Detector Tests
Detector Tests By Zone
Unassigned Detector Tests
If the devices have been assigned to Zones (on a pre-programmed SIM CARD or via the
programming menus) then it is possible to test the detectors with limited or no sounder operation.
Before starting clear all faults, put the system into Active Mode, and press SYSTEM RESET.
In test mode whenever a detector is activated the LED on that detector will be illuminated and the
event will be reported on the main panel for 15 seconds. If selected, the sounders will also operate for
1 second.
Pressing TEST (QUEUE REVIEW) will report the Zones that are in Test Mode.
If the detectors have not been assigned to a Zone then they can only be tested in normal (Active)
mode. Using the programming menu ensure the system is set to Active Mode then exit programming
mode and press SYSTEM RESET.
Carry out a fire test on each detector. Confirm the LED lights on the detector under test. Confirm that
the fire is reported correctly at the Main Panel (and any Repeaters). Confirm that the sounders
operate.
Note that sounders and detectors can be inhibited or delayed using the advanced features in the
programming menus. If the sounders do not operate as expected first verify all the settings for the
sounders and the device under test.
Enter programming mode and select function 7-3 Sounders on Test Activation. This allows you to
choose an audible confirmation that a device has detected a fire. The audible confirmation consists of
a 1 second period of sounder operation.
ALL SOUNDERS ON DETECTOR TEST activates the Main Panel Conventional Sounders and all
Conventional Sounders and Loop Sounders on the Sub-panel under test.
SUB_PANEL SOUNDERS ON DETECTOR TEST only operates the Conventional Sounders
Now select function 7-4 Test Zones to select the Zones which will be tested.
Exit programming mode, but DO NOT press SYSTEM RESET as this clears all test modes.
and Loop
Sounders on the Sub-panel under test. I.e. The Sub-panel that the detector under test is physically
connected to.
COMMISSIONING