9000-0447 Rev. I
Page 34 of 42
5.3 WALK / DRILL Menu Selections
Drill ON/OFF
Is a simple ON or OFF selection. ON will activate the NACs, while
OFF will deactivate them.
Audible Test
Is a simple ON or OFF selection for an audible walk test. The
audible appliances will sound twice for a trouble, 3 times for a
supervisory signal and 4 times for an alarm.
5.4 I/O Menu Selections
Output ON/OFF
Forces the toggling on or off of a specified output. These
outputs can include NAC 1, NAC 2, Municipal Circuit (if
present) and any Addressable Control Point.
Enable/Disable
Allows the user to take any addressable device on either SLC
and disconnect it through software. While disabled, a point will
report a trouble until it is enabled, but will not cause or
respond to an alarm.