535 User's Manual Chapter 5 43
Controller Set Up
Access Set Up Return to Operation Next menu Next parameter Next value Access Tuning Return to Operation
+
FAST MENU
DISPLAY
+
MENU MENU
▲ ▼
MENU DISPLAYFAST
8. ACK.:1
Defines whether alarm 1 may be acknowledged.
D ENABLED Allows the alarm to be acknowledged
• DISABLED Prevents the alarm from being acknowledged
while in alarm condition
9. POWER UP:1
Defines how alarm 1 will be treated on power up.
D NORMAL Alarm depends on process variable
• ALARM Always power up in alarm regardless of PV
• DELAYED Must leave alarm condition and reenter before
activating the alarm
10. MESSAGE:1
A 9-character message associated with alarm 1. To enter message: The first
character of third display will be flashing. Press the
▲▲
▲▲
▲ and
▼▼
▼▼
▼ keys to scroll
through the character set. Press FAST key to advance to subsequent
characters. Press the MENU to advance to next parameter.
D ALARM 1.
11. ALM. TYPE:2
Defines the type of alarm for alarm 2.
• HIGH ALRM.
• LOW ALARM
• HIGH/LOW Separate High & Low alarm setpoints in one
alarm
• BAND
• DEVIATION
• MANUAL Causes an alarm when in manual control
• REMOTE SP Causes an alarm when in Remote Setpoint
• RATE Selects a rate-of-change alarm
D OFF Deactivates the first alarm
12. ALM. SRC:2
Selects the source of the value being monitored by HIGH, LOW or HIGH/LOW
alarm 2.
D PV
•SP
• RAMP SP
• DEVIATION
• OUTPUT
• PV2
ALM.SRC.:2
PV
ALM. TYPE:2
OFF
POWER UP:1
NORMAL
ACK.:1
ENABLED
MESSAGE:1
ALARM 1